AF COLLAR C

 

AF COLLAR C is made of stainless steel. The interior contains AF Firefill 50/70/100, a high intumescent power material which is retained by a mechanism. During a fire, the pipe deforms due to the heat and melts until its complete combustion. Meanwhile, the intumescent material spreads and creates a barrier providing thermal insulation and preserving the floor or wall "separating" function of the element for at least 180 minutes.

 

AF COLLAR C is a special fire protection element for combustible pipes suitable for curved or branched pipes adjacent to walls/floors where it is impossible to apply normal firestop collars.

Its “C” shape avoids the need for calcium silicate protection boxes, which are more complex and expensive due to their long construction times.

 


Download Brochure
Share

Species bassus zeta est. Varius hibrida foris perderes vita est. Peregrinationes nunquam ducunt ad noster elevatus. Nunquam manifestum demissio. Danistas sunt lunas de secundus zirbus. Scutums sunt triticums de flavum capio.

Your Comment

CHARACTERISTICS

Appearance: stainless steel “C” shaped element;

Colour: polished steel;

Available sizes: 110, 160, 200, 250 and 400 mm;

Free expansion: >20:1;

Activation temperature: 180°C.

 

APPLICATION METHOD:

  1. place the AF COLLAR C around the combustible pipe so that it can adhere to the wall flush opening (on the fire-exposed side);
  2. if applied to floors and concrete walls, secure with metal plugs (8x60 mm). If applied on plasterboard walls use self-tapping metal screws.

 

TESTED WALL AND FLOOR APPLICATIONS

 

Type

Pipe diameter

External size

Height

AF COLLAR C 110

Up to 110

160x160 mm

50 mm

AF COLLAR C 160

From 110 to 160 mm

230x230 mm

70 mm

AF COLLAR C 200

From 160 to 200 mm

300x300 mm

100 mm

AF COLLAR C 250

From 200 to 250 mm

350x350 mm

100 mm

AF COLLAR C 400

From 250 to 400 mm

450x450 mm

150 mm

PACKAGING AND STORAGE

Cardboard boxes.

If the product is stored under standard conditions, there is no storage time limit

 

SPECIFICATIONS

Supply and application of the AF COLLAR C firestop collars. They have a stainless steel square structure and a locking system which contains Firefill 50/70/100 intumescent material for EI 180 protection of curved combustible pipe flush penetrations. The size will be chosen depending on the combustible pipe section.

 

CERTIFICATIONS

Class EI 180 (EN 1366-3) Concrete floor

Class EI 180 (EN 1366-3) Gasbeton wall

Class EI 120 (EN 1366-3) Plasterboard wall

 

Here you can read some details about a nifty little lifecycle of your order's journey. At first you choose the product you like. Then you put into your shopping cart and pass the checkout process in a few clicks. Our store offers several payment and delivery methods, so you have an opportunity to choose which one is the most convenient for you.